3 Installation
3.6 Electrical Installation
88 DC1…20… and DC1…OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
3.6.1.5 IP66
Figure 45: Stripping lengths in the power section
Mains = Electrical power network (supply voltage)
Motor = Motor connection
DC link = Internal DC link (DC link coupling)
Brake Resistor = Braking resistance (connection to brake chopper)
Table 9: Terminal capacities and tightening torques
Mains 1~ Mains 3~ Motor Brake Resistor
A1
PE
A1
PE
A1
PE
A1
PE
Baugröße Screw A1 Maximum terminal
capacity
Tightening torque
DC1-…-A66… DC1-…-A6S…
Mains Motor
Typ mm (in) mm
2
(AWG) Nm (lb-in) Nm (lb-in) Nm (lb-in)
FS1 M4 10 (0.39) 8 (8) 1 (8.85) 0.8 (7.08) 1 (8.85)
FS2
M4 10 (0.39) 8 (8) 1 (8.85) 0.8 (7.08) 1 (8.85)
FS3
M5 10 (0.39) 8 (8) 1 (8.85) 0.8 (7.08) 1 (8.85)
FS4
M6 10 (0.39) 16 (6) 2.2 (19.47) 2 (17.70) 2.2 (19.47)

Table of Contents