5 Parameters
5.6 Operational data indicator
DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com 103
5.6 Operational data indicator
When the specified supply voltage is applied (L1/L, L2/N, L3), the 7-segment
LED display will light up (Power ON); the display will show Stop.
You can use arrow keys and to select the operational data indicator you
want (parameter number P00-…) in the "Monitor" (P-00…) menu. You can tell
the display to stop alternating between the parameter number and the
display value and only show the display value instead by pressing the OK
button. In order to access other operational data indicators, you will have to
press the OK button again. You can then make your selection using the
and arrow keys and confirm it with the OK button.
The values of the operating data display cannot be changed by
hand (i. e. by value entry).
PNU ID Access
right
Value Description
ro/rw
P-00 - Display values
P00-01 20 ro % Analog input 1
100 % = Maximum input voltage
P00-02 21 ro % Analog Input 2
100 % = Maximum input voltage
P00-03 22 ro Hz/rpm Frequency reference value / Motor shaft speed
Shown in Hz if P-10 = 0; otherwise shown in revolutions per minute
P00-04 11 ro Status
DI1 - DI4
Digital inputs 1 - 4
State of the variable frequency drive's digital input
P00-05 ro 0 Reserved
P00-06
ro 0 Reserved
P00-07 ro V Motor voltage: the value of the rms voltage being applied at the motor
P00-08
23 ro V Internal DC bus voltage
P00-09 24 ro °C Unit Temperature
Heatsink temperature in °C
P00-10 ro HH:MM:SS The variable frequency drive's operating time
Not affected when the parameters are reset to their default settings.
P00-11 ro HH:MM:SS The variable frequency drive's operating time since the last trip
Operating time clock stopped by variable frequency drive lockup (or trip). Reset with next
enable only if a trip occurred. Also reset with next enable after the variable frequency
drive's mains power is switched off.
P00-12 ro HH:MM:SS The variable frequency drive's operating time since the last trip
Operating time clock stopped by variable frequency drive lockup (or trip). Reset with next
enable only if a trip occurred (undervoltage does not count as a trip) – Not reset when mains
power is switched off/on unless a trip occurred before the mains power was switched off.