7 Applications
7.4 Fixed frequency setpoint values
DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com 125
Figure 77: Example: Activation of the fixed frequencies with acceleration and deceleration
ramps
The change between the individual fixed frequencies is done with the accel-
eration times and deceleration times set at P-03 and P-04. ( Figure 77).
When the FWD or REV enables are revoked, the output frequency is inhib-
ited directly (coasting to halt).When P-05 = 0, the drive performs a
controlled deceleration .
7.4.2 Frequency jump
In systems with mechanical resonances, you can skip this frequency range
for stationary operation.
Figure 78:Setting range for frequency masking
a P-26
b P-27
f
[Hz]
DI3
DI4
DI1
f
max
(50 Hz)
FF4 = 40 Hz
FF3 = 30 Hz
FF1 = 15 Hz
FF2 = 20 Hz
0 Hz
P-01
P-04P-03
FWD
①
②
①
t [s]
P-05 = 0
②
STOP
f
[Hz]
②
①
t