10 Error Messages
10.2 Error Messages
164 DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
The example below shows how to access the fault log.
View Explanation
Operating state Stop
Press the OK button and hold it down for two seconds.
The parameter that was last accessed will be shown.
The last digit on the display will flash.
Use the (Up) or (Down) arrow buttons to select parameter P-13 and
confirm your selection by pressing the OK pushbutton.
Last error message.
Example: P-def (Parameter default = Default settings loaded).
Use the arrow key (Up) to go to the next error message.
Second most recent error message:
Example: V-Volt (undervoltage message). The dot on the right will flash.
The third most recent error message will be shown after pressing
the arrow key (Up).
Example: E-trip (external error message).
The two dots on the right will flash.
The oldest error message will be shown after you press the arrow key
(Up) once more.
Example: V-Volt (undervoltage message)
The three dots on the right will flash.