11 Annex
11.3 Technical data
DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com 179
11.3.4 DC1-34
Symbol
Unit
DC1-
342D2…
DC1-
344D1…
DC1-
344D1…
DC1-
345D8…
DC1-
349D5…
Main circuit
Feeder unit
Rated operating voltage U
e
V AC 400, 3-phase
Mains voltage (50/60Hz) U
LN
V 380 (-10 %) - 480 (+10 %)
Input current I
LN
A 2.4 4.3 4.3 6.1 9.8
Mains frequency f
LN
Hz 50/60
Frequency range f
LN
Hz 48 - 62
Power section
Overload current for 60 s every 600 s I
L
A 3.3 6.15 6.15 8.7 14.25
Starting current for 2 s every 20 s I
L
A 3.85 7.18 7.18 10.15 16.63
Output voltage at U
e
U
2
V AC 400, 3-phase
Output frequency f
2
Hz 0 -50 Hz (max. 500)
Pulse frequency f
PWM
kHz 16 (adjustable 4 – 32)
Frequency resolution (setpoint value) ΔfHz0.1
Rated operational current
1)
I
e
A 2.2 4.1 4.1 5.8 9.5
Heat dissipation
Heat dissipation of rated operational
current
P
V
CO 63.75 76.5 76.5 101.2 136
Efficiency η %
91.5 94.9 94.9 95.4 96.6
Maximum leakage current to earth (PE)
without motor
I
PE
mA < 1 < 1 < 1 < 1 < 1
Fan, built-in
✓ ✓ ✓ ✓ ✓
Size
Size FS1 FS1 FS2 FS2 FS2
Motor feeder
Assigned motor output
at 400 V, 50 Hz P kW 0.75 1.5 1.5 2.2 4
at 440 - 480 V, 60 Hz P HP
1 2 2 3 5
Apparent power
Apparent power at rated operation
400 V
SkVA1.52 2.84 2.84 4.02 6.58
Apparent power at rated operation
480 V
SkVA