11 Annex
11.19 List of parameters
DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com 223
P-18 146 ✓ rw K1 signal (Relay Output 1) 0 118; 130;
AP040030
0 RUN, enable (FWD, REV)
1 READY, variable frequency drive ready for operation
2 Output frequency = frequency reference value
3 Error message (variable frequency drive not ready)
4 Output frequency ≧ limit value (P-19)
5 Output current ≧ limit value (P-19)
6 Output frequency < limit value (P-19)
7 Output current < limit value (P-19)
P-19 147 ✓ rw 0 - 200.0 % K1-Limit value (relay) 100.0 118, 131;
AP040030
P-20
148 ✓ rw 0 - 50 Hz Fixed frequency FF1 / speed 1 15.0 124; AP040038
P-21 149 ✓ rw 0 - 50 Hz Fixed frequency FF2 / speed 2 0.0 124; AP040038
P-22 150 ✓ rw 0 - 50 Hz Fixed frequency FF3 / speed 3 0.0 124; AP040038
P-23
151 ✓ rw 0 - 50 Hz Fixed frequency FF4 / speed 4 0.0 124; AP040038
P-24 152 ✓ rw 0.1 - 25.0 s Second deceleration time (dec2) 0.0 107; AP040016
P-25 153 ✓ rw AO1 signal (Analog Output)
Switch to digital output
8 119, 131
DO1 (digital output 1) → +24 VDC (values 0 - 7)
0 RUN (variable frequency drive enabled and running –
FWD, REV)
1 READY, variable frequency drive ready for operation
/ no faults
2 Output frequency = frequency reference value
3 Error message (variable frequency drive is not ready)
4 Output frequency ≧ limit value (P-19)
5 Output current ≧ limit value (P-19)
6 Output frequency < limit value (P-19)
7 Output current < limit value (P-19)
Analog output → 0 - 10 V DC (value 8, 9)
8 Output frequency f-Out → 0 - 100 % f
max
(P-01)
9 Output current → 0 - 200 % I
e
(P-08)
P-26 154 ✓ rw 0.00 - 50.00 Hz Frequency skip 1, bandwidth (hysteresis range) 0 126; AP040026
P-27 155 ✓ rw 0.00 - 50.00 Hz Frequency skip 1, center 0 126; AP040026
P-28 156 – rw 0.00 - P-07 V V/Hz characteristic curve modification voltage 0 114; AP040036
P-29 157 – rw 0.00 - P-09 Hz V/Hz characteristic curve modification frequency 0 114; AP040036
PNU
ID Access right Value Description DS Page / Appli-
cation note
RUN ro/rw