11 Annex
11.19 List of parameters
224 DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
P-30 158 ✓ rw REAF, Start function with automatic restart, control
signal terminals
Ed9E-r 132; AP040028
0 = Ed9E-r Disabled
1 = AVto-0 Automatic start
2 = AVto-1 Automatic start: once
3 = AVto-2 Automatic start: two times
4 = AVto-3 Automatic start: three times
5 = AVto-4 Automatic start: four times
6 = AVto-5 Automatic start: five times
P-31 159 ✓ rw Start function with automatic restart, operating unit. 1 129; AP040028
0 Minimum frequency/speed; keypad
1 Previous speed, keypad
2 Minimum frequency/speed; terminal
3 Previous speed, terminal
P-32
160 ✓ rw 0 - 25 s DC current braking 0 119
P-33 161 ✓ rw Motor pick-up control function (to catch spinning
motors) (in sizes FS2 and FS3) / DC braking, braking
time at start (in size FS1)
0 119
0 Deactivated
1 Activated
P-34
162 ✓ rw Brake chopper activation
(in sizes FS2 and FS3)
0 119; AP040024
0 Locked
1 Enabled with overload protection braking resistance
2 Enabled without overload protection braking resis-
tance
P-35
163 ✓ rw 0 - 500 % Analog input 1 scaling 100 122
P-36
164 – rw Serial communication configuration 138, 153
1 - 63 Variable frequency drive slave address 1
Modbus RTU baud rate 6
2 9.6 kBit/s
3 19.2 Kbit/s
4 38.4 kBit/s
5 57.6 kBit/s
6 115.2 kBit/s
TimedOut 3000 138, 154
0 0
1 t 30 ms
2 t 100 ms
PNU ID Access right Value Description DS Page / Appli-
cation note
RUN ro/rw