11 Annex
11.19 List of parameters
DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com 225
3 t 1000 ms
4 t 3000 ms
5 r 30 ms
6 r 100 ms
7 r 1000 ms
8 r 3000 ms
P-37
165 rw 0 - 9999 Access code definition 101 97; AP040020
P-38
166 rw Parameter access lock 0 97; AP040020
0 Deactivated
1 Activated
P-39 167 rw -500.0 - +500.0 % Offset for analog input 1 0.0 AP040024
P-40 168 rw 0.00 - 6,000 Speed display scaling factor 0.00 AP040034
P-41 169 rw 0.0 - 30.0 PI controller, proportional gain 1.0
P-42 170 rw 0.0 - 30.0 s PI controller, integral time 1.0
P-43 171 rw PI controller, operating mode 0
0 direct operation
1 Reverse action
P-44
172 rw PI controller, reference value/setpoint value 0
0 Digital, preset setpoint value (P-45)
1 Analog input 1
P-45
173 rw 0.0 - 100.0 % PI digital setpoint value 0.0
P-46 174 rw PI controller, feedback 0
0 Analog input 2
1 Analog input 1
2 Motor current
P-47
175 rw Analog input 2 (AI2), signal range t 4-20 121; AP040024
0 = V 0-10 0 - 10 V signal
1 = A 0-20 0-20mA
2 = t 4-20 4-20mA ( 3mA error message: 4-20F)
3 = r 4-20 4 - 20 mA ( 3mA delay time 1)
4 = t 20-4 20 - 4 mA ( 3mA error message: 4-20F)
5 = r 20-4 20 - 4 mA ( 3mA delay time 1)
P-48 176 rw 0.1 - 25.0 s Standby-time 20
0 Deactivated
P-49 177 rw 0.0 - 100.0 % PI controller, feedback wakeup level 0
PNU ID Access right Value Description DS Page / Appli-
cation note
RUN ro/rw