EasyManua.ls Logo

Eaton PowerXL DC1 Series - Page 27

Eaton PowerXL DC1 Series
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 DC1 device series
1.7 Features
DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com 21
h Motor connection with output voltage U
2
(0 to 100% U
e
) and output frequency f
2
(0 to 500 Hz)
The connection in the motor feeder is implemented with a screened cable that is earthed on both sides
across a large area (PES).
Rated operational current (I
e
, output current):
DC1-1D…: 2.3 - 5.8 A
DC1-12…: 2.3 - 15 A
DC1-32…: 2.3 - 18 A
DC1-34…: 2.2 - 24 A
100% at an ambient temperature of +50 °C with an overload capability of 150% for 60 s
and a starting current of 175% for 2 s.
i Three-phase asynchronous motor
Continuously variable speed control for motors with the rated motor shaft outputs (P
2
):
DC1-1D…: 0.37 - 1.1 kW (230 V, 50 Hz) or 0.5 - 1.5 HP (230 V, 60 Hz)
DC1-12…: 0.37 - 4 kW (230 V, 50 Hz) or 0.5 - 5 HP (230 V, 60 Hz)
DC1-32…: 0.37 - 4 kW (230 V, 50 Hz) or 0.5 - 5 HP (230 V, 60 Hz)
DC1-34…: 0.75 - 11 kW (400 V, 50 Hz) or 1 - 15 HP (460 V, 60 Hz)
j Control section with operating unit and control buttons, seven-segment display, control voltage,
plug-in control signal terminals
k RJ45 interface for the computer and fieldbus connection (OP bus, Modbus RTU, CANopen)

Table of Contents

Other manuals for Eaton PowerXL DC1 Series

Related product manuals