3 Installation
3.3 EMC installation
52 DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
Route mains and motor cables in the switch cabinet as close to
the ground potential as possible. This is because free moving
cables act as antennas.
When laying HF cables (e.g. screened motor cables) or
suppressed cables (e.g. mains supply cables, control circuit and
signal cables) in parallel, a minimum clearance of 300 mm
should be ensured in order to prevent the radiation of electro-
magnetic energy. You should also use separate cable entries if
there is a great difference in voltage potentials. Any necessary
crossed cabling between the control signal and power cables
should always be implemented at right angles (90 degrees).
Never lay control- or signal cables in the same duct as power
cables. Analog signal cables (measured, reference and correc-
tion values) must be screened.