3 Installation
3.5 Electrical Installation
70 DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
The DC1 variable frequency drive has four control inputs (control signal termi-
nals 2, 3, 4, and 6). Two of these are parameterizable as digital control inputs;
while the others can be set to work as digital or analog control inputs.
The variable frequency drive comes with the following default setting:
Control signal terminal 2 as digital input 1 (DI1),
Control signal terminal 3 as digital input 2 (DI2),
Control signal terminal 4 as digital input 3 (DI3),
Control signal terminal 6 as analog input 1 (AI1).
Control signal terminal 8 can be used as a digital or as an analog output. It is
used as an analog output (AO) in the default configuration that comes with
the variable frequency drive when it is delivered.
Figure 46: Control signal terminals (digital / analog)
2
DI1
FWD
24 V
3
DI2
REV
4
DI3
(AI2)
FF1
6
AI1
(DI4)
f-Soll
1
+24 V Out
< 100 mA
8
AO
(DO)
f-Out
CPU
0...+10 V/20 mA
0...+10 V/20 mA