3 Installation
3.5 Electrical Installation
DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com 71
3.5.2.6 Analog input signals
Depending on how parameters P-12 and P-15 are set, control signal termi-
nals 4 (AI2) and 6 (AI1) can be connected to analog signals:
0 - 10 V,
0 - 10 V with scaling and operating direction change,
0 - 20 mA
4 - 20 mA or 20 - 4 mA with open-circuit monitoring (< 3 mA) .
3.5.2.7 Analog output signal
An analog voltage signal (0 - 10 V) is available on control signal terminal 8.
This output can handle a maximum load of 20 mA.
The output signal is adjusted with parameter P-25 ( Page 119).
Figure 47: Analog output (AO)
(connecting example)
Control signal terminals 7 and 9 are the common 0 V reference
potential for all analog and digital input signals.
Control signal terminals 7 and 9 are the common 0 V reference
potential for all analog and digital input signals.
9
0...+10 V
AO
8
OV
< 20 mA
f-Out
-
+