4 Operation
4.6 Commissioning with field bus / SmartWire-DT
92 DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
4.6 Commissioning with field bus / SmartWire-DT
When using a field bus / SmartWire-DT, you will need to use parameter P-12
to select the desired field bus / SmartWire-DT.
Parameter P-36 is used to set the slave address for the field bus mode.
In order to control the device via a field bus / SmartWire-DT,
control signal terminals 1 and 2 must be connected with a
jumper in order to get an enable signal.
For more information, please refer to chapters 7 and 8.
For more information on SmartWire-DT, please refer to manual
MN04012009Z, "DX-NET-SWD. SmartWire-DT Interface Card
for DC1 Variable Frequency Drives."