5 Parameters
5.6 Operational data indicator
104 DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
Example: Status displays
The status displays of the digital inputs and outputs are equivalent. They can
be used to check whether an output control signal (e.g. from an external
controller) is activating the variable frequency drive's inputs (DI1 - DI4). This
provides you with an easy way to check the wiring (wire breakage).
The following table shows a few examples.
Display value: 1 = Activated = High; 0 = Not activated = Low
P00-13 ro HH:MM:SS The variable frequency drive's operating time since the last lockup
The variable frequency drive's operating time clock was stopped with the lockup.
Reset the value on next enable signal.
P00-14 ro 4 - 32 kHz Pulse frequency
The variable frequency drive's actual effective output pulse frequency. If the variable
frequency drive gets too hot, this value can be lower than the frequency selected in P-17.
The variable frequency drive will automatically reduce the pulse frequency in order to
prevent a trip due to excess temperature and keep the system going.
P00-15
ro 0 - 1000 V DC bus voltage log (256 ms)
The eight most recent values before the trip
Updated every 250 ms.
P00-16 ro -20 - 120 °C Heat sink temperature memory
The last eight values before the trip. Updated every 500 ms.
P00-17
ro (0 - 2) x rated
operational
current
Motor current memory
The last eight values before the trip. Updated every 250 ms.
P00-18 15 ro Control section software version
16 Power section software version
P00-19 ro Serial number of variable frequency drive
Unique variable frequency drive serial number (example: 540102 / 32 / 005)
P00-20 12 ro Variable frequency drive part no.
13 Rated power of variable frequency drive
14 Firmware Version
PNU
ID Access
right
Value Description
ro/rw
PNU ID Display value Description
P00-04 11 0000 No digital input (DI1, DI2, DI3, DI4) is actuated
1000 Control signal terminal 2 actuated (DI1)
0100 Control signal terminal 3 actuated (DI2)
0010 Control signal terminal 4 actuated (DI3)
0001 Control signal terminal 6 actuated (DI4)
0101 Control signal terminals 3 and 6 actuated (DI2 + DI4)