5
Step 2 — Keypad overview
POWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040012EN—December 2017 www.eaton.com
LED lights
Table 3. LED state indicators
Indicator Description
Run
Green Run:
Indicates that the VFD is running and controlling the load in
Drive or Bypass.
Blinks when a stop command has been given but the drive is
still ramping down.
Fault
Red Fault:
Turn on when there is one or more active drive fault(s).
Blinks when there is one or more active drive warning(s).
Remote
Yellow Local/Remote:
Local: If the local control place is selected, turn off the light.
Remote: If the remote control place is selected, turn on the
light.
LCD display
The keypad LCD indicates the status of the motor and the
drive and any faults in motor or drive functions. On the
LCD, the user sees information about the current location in
the menu structure and the item displayed.
Overview
Five lines shall be displayed in the screen. General view is
as following in Figure 4.
Figure 4. General view of LCD
Drive Status
Direction Status
Control Place
Menu Location
Soft Key 2
Function Label
Soft Key 1
Function Label
Real Time Clock
(hh:mm)
Active
Se
lection
The lines definition is as below:
The first line is State line, shows:
RUN/STP/NRD/FIM/TFM — If motor is running, the
run state shall display “RUN”, otherwise the state display
“STP”. “RUN” blinks when the stop command is sent but
the drive is decelerating. “NRD” is displayed if the drive
is not ready or does not have a signal “FIM” is displayed
to indicate it is in Fire Mode and the drive is in a Run
state. “TFM” is displayed when in the Fire Mode Test
Mode and the drive is in a Run State.
FWD/REV/JOG — If the motor running direction is
clockwise, display “FWD”, otherwise display “REV” “Jog”
if the drive is in Jog mode the status indication will occur.
KEY/I/O/BPS/RBP/BUS/OFF — If it is in bypass
currently, display “BPS”; when run command is given it
will got to “RBP”. otherwise, if the current control source
is I/O terminal, display “I/O. If it is keypad, then display
“KEY”; otherwise display “BUS.” if HOA enabled and
switch to OFF, it shall show OFF.
PAR/MON/FLT/OPE/QSW/FAV/TPM/MS1/SL1/SL2/
SL3/SL4/BUx. — If the current page is parameter menu,
display “PAR”; If monitor menu, then display “MON”; If
fault menu, then display “FLT”; If operation menu, then
display OPE”; If quick start wizard, then display “QSW”;
If optional card menu, then display “BOA”; If favorite
menu, then display “FAV”; If main menu, then display
“TPM” when doing the Multi-drive Pump and Fan mode,
the drive mode will be defined with MS- Master and
SL being a slave drive. The 1 through 5 will indicate the
number in the series it is. “BUx” indicates the drive being
a backup drive when in the redundant drive system.
The second line is Code line, shows the menu code.
The third line is Name line, shows the menu name or
parameters name.
The fourth line is Value line, shows the submenu name or
parameters value.
The fifth line is Soft key line, the functions of Soft key 1 and
Soft key 2 are changeable, and the real time is in the middle.