Analog value object instance summary
The following table summarizes the Analog Value Objects supported.
Table 100. Analog value object instance summary
Instance ID Object name Description Units
Preset value
access
AV0 Frequency set point Frequency set point Hz R
AV1 Output frequency Output frequency Hz R
AV2 Motor speed Motor speed Rpm R
AV3 Motor load Motor shaft power Percent R
AV4 Megawatt hours total Megawatt hour counter (total) MWh R
AV5 Motor current Motor current Amps R
AV6 Dc link voltage Dc link voltage Volts R
AV7 Motor voltage Motor voltage Volts R
AV8 Unit temperature Heatsink temperature °C R
AV9 Motor torque Motor torque Percent R
AV10 Operating days Operating days (resettable) Day R
AV11 Operating hours Operating hours (resettable) Hour R
AV12 Torque reference Torque reference Percent R
AV13 Motor temperature Motor temperature Percent R
AV14 Active fault code Latest active fault code No Units R
AV15 Speed reference Motor speed reference from network % C
AV16 Current limit Current limit Amps W
AV17 Min frequency Minimum frequency Hz W
AV18 Maximum frequency Maximum frequency Hz W
AV19 Accel time 1 Acceleration time seconds W
AV20 Decel time 1 Deceleration time seconds W
AV21 Anyparam id Parameter id number to be accessed No Units W
AV22 Anyparam value Value of parameter defined by av21 No Units W
AV23 Analog input 1 Analog input 1 Volts R
AV24 Analog input 2 Analog input 2 Volts R
AV25 Analog output 1 Analog output 1 Volts R
AV26 Analog output 2 Analog output 2 Volts R
ote:N For Present Value Access Types, R = Read-only,
W = Writeable, C = Commandable. Commandable
values support priority arrays and relinquish defaults.