EasyManua.ls Logo

Eaton PowerXL DG1 Series - Table 165. Instance 111 (Output) Length = 20 Bytes

Eaton PowerXL DG1 Series
195 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
129
DeviceNet external communication cards
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
Assembly instance 111
Table 165. Instance 111 (Output) length = 20 bytes
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 NetRef NetCtrl FB Input Data 2 FB Input Data 1 FaultReset Direction Run
1 NA
2
FBSpeedReference (Low Byte)
3
FBSpeedReference (High Byte)
4 ProcessDataIn1 (LowByte)
5 ProcessDataIn1 (HighByte)
6 ProcessDataIn2 (LowByte)
7 ProcessDataIn2 (HighByte)
8 ProcessDataIn3 (LowByte)
9 ProcessDataIn3 (HighByte)
10 ProcessDataIn4 (LowByte)
11 ProcessDataIn4 (HighByte)
12 ProcessDataIn5 (LowByte)
13 ProcessDataIn5 (HighByte)
14 ProcessDataIn6 (LowByte)
15 ProcessDataIn6 (HighByte)
16 ProcessDataIn7 (LowByte)
17 ProcessDataIn7 (HighByte)
18 ProcessDataIn8 (LowByte)
19 ProcessDataIn8 (HighByte)
This is the reference1 to the frequency converter. Used normally as Speed reference. The allowed scaling is 0 to 10000.
In the application, the value is scaled in percentage of the frequency area between set minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%).