131
DeviceNet external communication cards
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
Assembly instance 73
Table 168. Instance 73 (Input) length = 6 bytes
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 AtReference RefFromNet CtrlFromNet Ready Running2 Running1 Warning Faulted
1
Drive State
2 Speed actual (Low Byte), rpm
3 Speed actual (High Byte), rpm
4 Torque actual (Low Byte), Nm
5 Torque actual (High Byte), Nm
Refer “State transition diagram,” provided under “Control Supervisor Object” and “Drive State” table specified at end
of “Input Instances” section.
Drive State
0x00 DN_NON_EXISTANT
0x01 DN_STARTUP
0x02 DN_NOT_READY
0x03 DN_READY
0x04 DN_ENABLED
0x05 DN_STOPPING
0x06 DN_FAULT_STOP
0x07 DN_FAULTED
Assembly instance 75
Table 169. Instance 75 (Input) length = 6 bytes
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 AtReference RefFromNet CtrlFromNet Ready Running2 Running1 Warning Faulted
1
Drive State
2 Speed actual (Low Byte), rpm
3 Speed actual (High Byte), rpm
4
Process actual (Low Byte), Nm
5 Process actual (High Byte), Nm
Process actual value is same as process reference. This value will be a 0 to 10000 (100.00%) for use with Analog outputs
writing, 0 = 0 or 4 mA and 10000 being 20 mA.
Refer “State transition diagram,” provided under “Control Supervisor Object” and “Drive State” table specified at
end of “Input Instances” section.
Drive State
0x00 DN_NON_EXISTANT
0x01 DN_STARTUP
0x02 DN_NOT_READY
0x03 DN_READY
0x04 DN_ENABLED
0x05 DN_STOPPING
0x06 DN_FAULT_STOP
0x07 DN_FAULTED