EasyManua.ls Logo

Eaton PowerXL DG1 Series - Table 184. Control Supervisor Object, Class 0 X29

Eaton PowerXL DG1 Series
195 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
143
DeviceNet external communication cards
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
Control supervisor object, class 0x29
This object models all the management functions for devices within the “Hierarchy of
Motor Control Devices.The behavior of motor control devices is described by the
State Transition Diagram.
Table 184. Control supervisor object, class 0x29
Object descriptions
Class attributes
ID Description NV Data type Access rule Default Range
01h Revision NV UINT Get 1
02h Max instance NV UINT Get 1
03h Number of instances NV UINT Get 1
Class services
ID Service Requirements
0Eh Get attribute single
Instance attribute
ID Description NV Data type Access rule
03h Run1 V BOOL Get/Set 0 0–1
04h Run2 V BOOL Get/Set 0 0–1
05h NetCtrl V BOOL Get/Set 0 0–1
06h State V USINT Get 0 0–7
07h Running1 V BOOL Get 0 0–1
08h Running2 V BOOL Get 0 0–1
09h Ready V BOOL Get 0 0–1
0Ah Faulted V BOOL Get 0 0–1
0Bh Warning V BOOL Get 0 0–1
0Ch FaultRst V BOOL Get/Set 0 0–1
0Fh CtrlFromNet V BOOL Get 0 0–1
0Dh
Active fault code
V UINT Get 0 0–65535
6Ch
Comm idle action value
NV USINT Get/Set 2 0–2
6Dh Comm timeout NV UINT Get /Set 10 sec 0-60 sec
Instance services
ID Service
0Eh Get_attribute_single
10h Set_attribute_single
05h Reset Type 0
Notes
 See Appendix C for Active list of fault codes.
 Modification of Attribute 0x6C of Supervisory
Default value for this attribute to be Fault on idle Communication mode
This attribute to have 3 values as
0 = No Action (Hold Last State) in Idle Communication mode
1 = Stop Motor in Idle Communication mode
2 = Fault Motor in Idle Communication mode

Table of Contents