EasyManua.ls Logo

Eaton PowerXL DG1 Series - Process in Values; Table 188. Parameter ID List

Eaton PowerXL DG1 Series
195 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
166
Appendix A—Parameter ID list
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
Menu
Item No.
Modbus
Register
Profibus
PNU
Profibus
PNU
SubIndex
EtherNet/
IP Class
EtherNet/
IP Instance
EtherNet/
IP Attribute
DeviceNET
Class
DeviceNET
Instance
DeviceNET
Attribute Parameter Description
B16.1.2 1067 NA NA 162 1 202 NA NA NA Firmware Version
B16.1.3 2142 NA NA 164 1 101 NA NA NA Protocol Status
B16.2.1 1250 3201 200 163 1 120 NA NA NA Slave Address
B16.2.2 1251 3202 200 163 1 121 NA NA NA Baud Rate
B16.2.3 1252 3204 200 163 1 122 NA NA NA DO IO Data
B16.2.4 1253 3200 200 163 1 123 NA NA NA Operate Mode
B16.2.5 2520 NA NA NA NA NA NA NA NA Comm Card FB Fault
Response
B17.1.1 910 710 2 162 1 199 187 1 10 Board Status
B17.1.2 1067 NA NA 162 1 202 NA NA NA Firmware Version
B17.1.3 2143 NA NA 164 1 102 NA NA NA Protocol Status
B17.2.1 2144 NA NA 164 1 103 NA NA NA Node ID
B17.2.2 2145 NA NA 164 1 104 NA NA NA Baud Rate
B17.2.3 2146 NA NA 164 1 105 NA NA NA Operate Mode
B17.2.4 2520 NA NA NA NA NA NA NA NA Comm Card FB Fault
Response
B18.1.1 910 710 2 162 1 199 187 1 10 Board Status
B18.1.2 1067 NA NA 162 1 202 NA NA NA Firmware Version
B18.1.3 2147 NA NA 164 1 106 187 1 69 Protocol Status
B18.2.1 2148 NA NA 164 1 107 187 1 70 MAC ID
B18.2.2 2149 NA NA 164 1 108 187 1 71 Baud Rate
B18.2.3 2188 NA NA NA NA NA NA NA NA IO Poll Type
B18.2.4 2212 NA NA NA NA NA 41 1 109 Dnet Comm Timeout
B18.2.5 2520 NA NA NA NA NA NA NA NA Comm Card FB Fault
Response
O1 1 502 0 160 1 1 160 1 1 Output Frequency
O2 24 1 0 160 1 2 160 1 2 Freq Reference
O3 2 503 0 4 70 3 4 70 3 Motor Speed
O4 3 504 0 160 1 4 160 1 4 Motor Current
O5 4 507 0 160 1 5 160 1 5 Motor Torque
O6 5 513 1 160 1 6 160 1 6 Motor Power
O7 6 501 0 160 1 7 160 1 7 Motor Voltage
O8 7 501 1 160 1 8 160 1 8 DC-link Voltage
O9 8 822 6 160 1 9 160 1 9 Unit Temperature
O10 9 822 4 160 1 10 160 1 10 Motor Temperature
R11 782 2 2 162 1 138 161 1 11 Keypad Torque Ref
R12 141 1 8 160 1 155 161 1 12 Keypad Reference
R13 1307 2170 0 160 1 226 170 1 11 PID1 Keypad Set Point 1
R14 1309 2179 0 160 1 227 170 1 12 PID1 Keypad Set Point 2
Table 188. Parameter ID list, continued

Table of Contents

Related product manuals