POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
EMC directive
For the electrical equipment installed in the EMC, directive
states that the equipment must not disturb the environment
and must be immune to other electromagnetic disturbances
in the environment. Table 3 indicates the requirements for
the control wiring to meet this directive.
Table 3. Control wiring requirements
Item Directive
Product
IEC 61800-2
Safety
UL 508C, IEC / EN 61800-5-1
EMC (at default
settings)
Immunity: EN / IEC 61800-3, 2nd environment
Radiated emissions: EN / IEC 61800-3 (Transient Testing
included), 1st environment
Conducted emissions: EN / IEC 61800-3
Category C1: is possible with external filter connected to
drive. Please consult factory
Category C2: with internal filter maximum of 10m motor
cablelength
Category C3: with internal filter maximum of 50m motor
cable length
Control cable grounding
It is recommended that the shielded cables be grounded
as shown in Figure 5. Strip the cable insulation required
allowing attachment to the frame with the grounding clamp.
Figure 5. Control cable grounding
Table 4. PowerXL series—DG1 general purpose drive option boards
DX G NET PROFB
Function
PROFIBUS = PROFIBUS
DEVICENET = DeviceNet
CANopen = CANopen
SWD = SmartWire
1
See Volume 6, CA08100007E,
Tab 2, PowerXL DG1 Accessories
for full offering
Series
G = General purpose
Type
NET = Communication card
EXT = I/O card
ACC = Accessory
SPR = Spare part
KEY = Keypad
CBL = Cable
Basic naming
DX = PowerXL Drive
ote:N
Will be available 2017.