68
EtherNet/IP On-Board communications
POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com
Assembly instance 127
Table 95. Instance 127 (Input). EIP drive status length = 20 bytes
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 CtrlFromNet At zero speed AtReference Alarm/Warning Faulted Direction Running Ready
1
Drive state
2
% Speed actual (Low Byte)
3
% Speed actual (High Byte)
4 ProcessDataOut1 (LowByte)
5 ProcessDataOut1 (HighByte)
6 ProcessDataOut2 (LowByte)
7 ProcessDataOut2 (HighByte)
8 ProcessDataOut3 (LowByte)
9 ProcessDataOut3 (HighByte)
10 ProcessDataOut4 (LowByte)
11 ProcessDataOut4 (HighByte)
12 ProcessDataOut5 (LowByte)
13 ProcessDataOut5 (HighByte)
14 ProcessDataOut6 (LowByte)
15 ProcessDataOut6 (HighByte)
16 ProcessDataOut7 (LowByte)
17 ProcessDataOut7 (HighByte)
18 ProcessDataOut8 (LowByte)
19 ProcessDataOut8 (HighByte)
See note 1 from Table 90 on Page 65.
This is the actual value from the frequency converter. The value is between 0 and 10000. In the application, the value is scaled
in percentage of frequency area between set minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%).
ote:N See Appendix B for Process Data Value defaults.
Table 96. Instance 128 (Input). EIP drive status length = 20 bytes
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 AtReference RefFromNet CtrlFromNet Ready Running2 Running1 Warning Faulted
1
Drive state
2
% Speed actual (Low Byte)
3
% Speed actual (High Byte)
4 ProcessDataOut1 (LowByte)
5 ProcessDataOut1 (HighByte)
6 ProcessDataOut2 (LowByte)
7 ProcessDataOut2 (HighByte)
8 ProcessDataOut3 (LowByte)
9 ProcessDataOut3 (HighByte)
10 ProcessDataOut4 (LowByte)
11 ProcessDataOut4 (HighByte)
12 ProcessDataOut5 (LowByte)
13 ProcessDataOut5 (HighByte)
14 ProcessDataOut6 (LowByte)
15 ProcessDataOut6 (HighByte)
16 ProcessDataOut7 (LowByte)
17 ProcessDataOut7 (HighByte)
18 ProcessDataOut8 (LowByte)
19 ProcessDataOut8 (HighByte)
This is the actual value from the frequency converter. The value is between 0 and 10000. In the application, the value is scaled
in percentage of frequency area between set minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%).