Appendix D—Safety instructions for UL and cUL
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
For 575 V Drive Series, required line and motor wire
torque, type and size range are listed in Table 81
Table 83. Required line and motor wire torque (575 V)
DG1
catalog number
DH1
catalog number Terminal type
Required
torque (in-lb) Required wire range
FR1
DG1-353D3xx-xxxx DH1-354D5XX-XXXX L1, L2, L3, DC+, DC-, R+, R-, U, V, W 5.3 14–10 AWG
DG1-354D5xx-xxxx DH1-357D5XX-XXXX 5.3 14–10 AWG
DG1-357D5xx-xxxx DH1-35010XX-XXXX 5.3 14–10 AWG
FR2
DG1-35010xx-xxxx DH1-35013XX-XXXX L1, L2, L3, DC+, DC-, R+, R-, U, V, W 15.6 12–6 AWG
DG1-35013xx-xxxx DH1-35018XX-XXXX 15.6 10–6 AWG
DG1-35018xx-xxxx DH1-35022XX-XXXX 15.6 10–6 AWG
FR3
DG1-35022xx-xxxx DH1-35027XX-XXXX L1, L2, L3, DC+, DC -, R+, R-, U, V, W 40 6–2 AWG
DG1-35027xx-xxxx DH1-35034XX-XXXX 40 6–2 AWG
DG1-35034xx-xxxx DH1-35041XX-XXXX 40 6–2 AWG
FR4
DG1-35041xx-xxxx DH1-35052XX-XXXX L1, L2, L3, DC+, DC-, R+, R-, U, V, W 95 4–1/0 AWG
DG1-35052xx-xxxx DH1-35062XX-XXXX 95 4–1/0 AWG
DG1-35062xx-xxxx DH1-35080XX-XXXX 95 2–1/0 AWG
FR5
DG1-35080xx-xxxx DH1-35100XX-XXXX L1, L2, L3, DC+, DC-, R+, R-, U, V, W 354 1/0 AWG350 kcmil
DG1-35100xx-xxxx DH1-35125XX-XXXX 354 2/0 AWG–350 kcmil
DG1-35125xx-xxxx DH1-35144XX-XXXX 354 3/0 AWG–350 kcmil
FR6
DG1-35144xx-xxxx DH1-35208XX-XXXX L1, L2, L3, DC+, DC-, R+, R-, U, V, W 480 2*(1/0300 kcmil)
DG1-35208xx-xxxx DH1-35250XX-XXXX 480 2*(2/0300 kcmil)
All Frame Sizes (FR1–FR6)
All models Control Terminal Block 4.5 28~12 (Sol) AWG,
30~12 (Str) AWG