16
Chapter 2—Engineering considerations
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Electrical power network
Input connection and configuration
The PowerXL Series frequency inverters can be connected
and operated with all control-point grounded AC power
networks (see IEC 60364 for more information).
Figure 8. AC power networks with grounded neutral
point (TN-/TT networks)
L1
L2
L3
N
TT
L1
L2
L3
N
PE
TN-C-S
L1
L2
L3
N
PE
TN-S
L1
L2
L3
PEN
TN-C
The frequency inverter can be applied to all types of power
networks above. If multiple frequency inverters with
single-phase supplies are to be connected, a symmetrical
distribution to the three external conductors shall be taken
into account. In addition, the total current of all single-phase
consumers is not to cause an overload of the neutral
conductor (N-conductor).
The connection and operation of frequency inverters to
asymmetrically grounded TN networks (phase-grounded
delta network “Grounded Delta”, USA) or neutral point
ungrounded or high-resistance grounded (>30 ohms)IT
networks is only conditionally permissible. In these networks
above-mentioned, the internal interference suppression filter
of frequency inverter must be disconnected (unscrew the
screw marked ‘EMC’, see “Installation in IT System” on
Page 52). Then the required filtering for EMC (electromagnetic
compatibility) is no longer present (degrade to Class T).
Measures for EMC are mandatory in a drive system in
order to meet the legal requirements for EMC and low
voltageregulations.
Good grounding measures are a prerequisite for the
effective insert of further measures such as shielding of
filters. Without respective grounding measures, further
steps are superfluous.
Input voltage and frequency
The standardized input voltages (IEC 60038, VDE017-1) for
energy suppliers (EVU) guarantee the following conditions at
the transition points:
•
Deviation from the rated value of voltage: Max. ±10%
•
Deviation in voltage phase balance: Max. ±3%
•
Deviation from rated value of the frequency: Max. ±4%
The board tolerance band of the PowerXL Series frequency
inverterconsiders the rated value for
European as (EU: ULN = 230 V/400 V, 50 Hz),
American as (USA: U
LN = 240 V/480 V, 60Hz) and
Canada as (CAN: U
LN = 600 V, 60 Hz) standard voltages:
•
230 V, 50 Hz (EU) and 240 V, 60 Hz (USA) at DG1/DH1-32_
•
400 V, 50 Hz (EU) and 480 V, 60 Hz (USA) at DG1/DH1-34_
•
600 V, 60 Hz (CAN) at DG1/DH1-35_
For the bottom voltage value, the permitted voltage drop
of 4% in the consumer circuits is also taken into account,
therefore a total of ULN –14%.
•
230 V device class (DG1/DH1-32_): 208 V –15% to
240 V +10% (177 V –0% to 264 V +0%)
•
400 V device class (DG1/DH1-34_): 380 V –15% to
500 V +10% (323 V –0% to 550 V +0%)
•
600 V device class (DG1/DH1-35_): 525 V –15% to
600 V +10% (446 V –0% to 660 V +0%)
The permitted frequency range is 50/60 Hz (45 Hz –0% to
66Hz +0%).
Input voltage balance
Due to the uneven loading on the conductor, and with
the direct connection of greater power ratings, deviations
from the ideal voltage form and asymmetrical voltages
can be caused in three-phase AC power networks. These
asymmetric divergences in the input voltage can lead
to different loading of the diodes in input rectifiers with
three-phase supplied frequency inverters, and as a result,
anadvance failure of this diode.
In the project planning for the connection of three-phase
supplied frequency inverters, consider only AC power
networks that handle permitted asymmetric divergences in
the input voltage ≤ +3%.
If this condition is not fulfilled, or symmetry at the
connection location is uncertain, the use of an assigned AC
choke is recommended.