Chapter 6—Installation requirements
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Figure 19. Mounting space
DANGER
5 MIN
06
16
%$&.
5(6(7
OK
5(027(
581
)$8/7
/2&$/
5(0
DANGER
5 MIN
06
16
%$&.
5(6(7
OK
5(027(
581
)$8/7
/2&$/
5(0
C
A
A
A
B
D
Table 29. Space requirements for mounting the PowerXL Series VFD and airflow
Frame
size
A
In (mm)
B
In (mm)
C
In (mm)
D
In (mm)
Cooling air required
CFM (m
3
/h)
FR0 0 0 3.94 (100) 1.97 (50) 16.5 (28)
FR1 (IP21) 0.79 (20) 1.58 (40) 3.94 (100) 1.97 (50) 14 (24)
FR1 (IP54) 0 0 3.94 (100) 1.97 (50) 14 (24)
FR2 (IP21) 1.18 (30) 2.36 (60) 6.30 (160) 2.36 (60) 55 (94)
FR2 (IP54) 0 0 6.30 (160) 2.36 (60) 55 (94)
FR3 0 0 7.87 (200) 3.15 (80) 85 (144)
FR4 0 0 11.81 (300) 3.94 (100) 153 (260)
FR5 3.15 (80) 6.30 (160) 11.81 (300) 7.87 (200) 232 (395)
FR6 0 0 15.75 (400) 12.99 (330) 230 V: 435 (739)
480 and 575 V: 400 (679)
otes: N The above guidelines apply unless testing has been completed to validate a design
outside of these recommendations.
Minimum clearances A and B for drives with Type 12 (IP54) enclosure is 0 mm (in).