Chapter 6—Installation requirements
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Power wiring selection
Motor cable connections are made to terminals U, V, and W.
Cable selection: Power and motor leads
•
Use UL approved heat-resistant copper cables only
•
75 °C or higher for all units rated
•
Line voltage/mains should be Class 1 wire only outside
North America
•
Refer to the following tables for cable sizing guidelines
• North America 208 V to 240 V: Appendix B
• North America 380 V to 500 V: Appendix B
• All other International 380 V to 600 V: Appendix B
Line (Mains) and motor cable installation
The input line and motor cables must be sized in accordance
with the rated PowerXL VFD input and outputcurrent.
If motor temperature sensing is used for overload protection,
the output cable size may be selected based on the motor
specifications.
Maximum symmetrical supply current is 100,000 A RMS for
all size PowerXL VFDs.
Input protection
Input protection devices are rated based on PowerXL rated
input and output current. For UL and cUL/CSA, refer to
AppendixD for proper sizing. For gG/gL (IEC 60269-1), refer
to Appendix B for proper sizing.
Consult with service representative for further information
about input protection requirements.
Brake chopper connection
Dynamic braking resistor connections are made to the R+
and R- terminal on the drive. Wire size should be followed
according to the wattage being transfered. Below are images
of the locations for wiring.
Figure 22. Brake resistor wiring
/ / / 8 9 :'&
'&5
5
Line Motor
%UDNH5HVLVWRU
Connection tightening torque
Table 31. Tightening torque
Frame
Size
Power wire
In-Lb (Nm)
Ground wire
In-Lb (Nm)
Control wire
In-Lb (Nm)
FR0 5.3 (0.6) 14 (1.6) 4.5 (0.5)
FR1 5.3 (0.6) 10 (1.1) 4.5 (0.5)
FR2 15.6 (1.8) 10 (1.1) 4.5 (0.5)
FR3 40 (4.5) 10 (1.1) 4.5 (0.5)
FR4 95 (10.7) 14 (1.6) 4.5 (0.5)
FR5 354 (40) 35 (4.0) 4.5 (0.5)
FR6 480 (54.2) 35 (4.0) 4.5 (0.5)
otes: N Strip the motor and power cables as shown in
Figure 23.
Both UL and IEC tools may be used.
Applies to strained wire, solid wire, or ferrule
installations.