40
Chapter 6—Installation requirements
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Figure 23. Input power and motor cable stripping
lengths
Table 36. Input power and motor cable stripping and wire lengths
Frame
Size
Power wiring in inches (mm) Motor wiring in inches (mm)
A1 B1 C1 D1 A2 B2 C2 D2
FR0 0.39
(10)
5.12
(130)
0.39
(10)
5.12
(130)
0.39
(10)
3.15
(80)
0.39
(10)
1.97
(50)
FR1 0.39
(10)
1.77
(45)
0.39
(10)
1.38
(35)
0.39
(10)
1.77
(45)
0.39
(10)
1.38
(35)
FR2 0.59
(15)
1.77
(45)
0.59
(15)
1.77
(45)
0.59
(15)
1.57
(40)
0.59
(15)
1.57
(40)
FR3 0.59
(15)
1.57
(40)
0.59
(15)
1.97
(50)
0.59
(15)
1.57
(40)
0.59
(15)
1.97
(50)
FR4 0.98
(25)
2.56
(65)
0.98
(25)
4.72
(120)
0.98
(25)
2.56
(65)
0.98
(25)
4.72
(120)
FR5 1.10
(28)
6.10
(155)
1.10
(28)
9.45
(240)
1.10
(28)
6.10
(155)
1.10
(28)
9.45
(240)
FR6 0.98
(25)
4.72
(120)
0.98
(25)
7.
87
(200)
0.98
(25)
4.72
(120)
0.98
(25)
7.87
(200)
Cable routing
If conduit is being used for wiring, use separate
conduits for line voltage (mains), motor cables, and all
interface/controlwiring.
To meet the UL requirements, if conduit is being used
for wiring, the enclosure openings provided for conduit
connections in the field shall be closed by UL listed conduit
fittings with the same type rating (Type 1 / Type 12) as
theenclosure.
Avoid running motor cables alongside or parallel to any other
wiring. If it is necessary to run motor cables with other
wiring, then maintain spacing between motor cables and
other wiring in accordance with Table 26.
Wiring the VFD
Refer to Table 27 and Table 28 for maximum cable lengths
by frame size.
If three or more motor cables are used, each conductor must
have its own overcurrent protection.