44
Chapter 6—Installation requirements
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
I/O Connection
•
Run 240 Vac and 24 Vdc control wiring in separate conduit
•
Communication wire to be shielded
Table 37. I/O connection
External
Wiring
Pin Signal name Signal Default setting Description
Res
i
1 +10 V Ref. Output voltage — 10 Vdc supply source
2AI1+
Analog input 1 0–10 V Voltage speed reference (programmable to 4 mA to 20 mA)
3 AI1– Analog input 1 ground — Analog input 1 common (ground)
4AI2+
Analog input 2 4 Ma to 20 ma Current speed reference (programmable to 0–10 v)
5 AI2– Analog input 2 ground — Analog input 2 common (ground)
6 GND I/O signal ground — I/O ground for reference and control
7 DIN5 Digital input 5 Preset speed b0 Sets frequency output to preset speed 1
8 DIN6 Digital input 6 Preset speed b1 Sets frequency output to preset speed 2
9 DIN7 Digital input 7 Emergency stop (ti–) Input forces VFD output to shut off
10 DIN8 Digital input 8 Force remote (ti+) Input takes VFD from local to remote
11 CMB Di5 to di8 common Grounded Allows source input
12 GND I/O signal ground — I/O ground for reference and control
13 24 V +24 Vdc output — Control voltage output (100 mA max.)
14 DO1 Digital output 1 Ready Shows the drive is ready to run
15 24 Vo +24 Vdc output — Control voltage output (100 mA max.)
16 GND I/O signal ground — I/O ground for reference and control
17 AO1+ Analog output 1 Output frequency Shows output frequency to motor 0–60 hz (4 mA to 20 mA)
18 AO2+ Analog output 2 Motor current Shows motor current of motor 0–fla (4 mA to 20 mA)
19 24 Vi +24 Vdc input — External control voltage input
20 DIN1 Digital input 1 Run forward Input starts drive in forward direction (start enable)
21 DIN2 Digital input 2 Run reverse Input starts drive in reverse direction (start enable)
22 DIN3 Digital input 3 External fault Input causes drive to fault
23 DIN4 Digital input 4 Fault reset Input resets active faults
24 CMA Di1 to di4 common Grounded Allows source input
25 A Rs-485 signal a — Fieldbus communication (modbus, bacnet)
26 B Rs-485 signal b — Fieldbus communication (modbus, bacnet)
27 R3NO Relay 3 normally open At speed Relay output 3 shows VFD is at ref. Frequency
28 R1NC Relay 1 normally closed Run Relay output 1 shows VFD is in a run state
29 R1CM Relay 1 common
30 R1NO Relay 1 normally open
31 R3CM Relay 3 common At speed Relay output 3 shows VFD is at ref. Frequency
32 R2NC Relay 2 normally closed Fault Relay output 2 shows VFD is in a fault state
33 R2CM Relay 2 common
34 R2NO Relay 2 normally open
The above wiring demonstrates a SINK configuration. It is important that CMA and CMB are wired to ground (as shown by dashed line).
If a SOURCE configuration is desired, wire 24 V to CMA and CMB and close the inputs to ground. When using the +10 V for AI1, it is
important to wire AI1—to ground (as shown by dashed line). If using +10 V for AI1 or AI2, terminals3,5, and 6 need to be jumpered together.
AI1+ and AI2+ use a 10k pot for 0–10 V.