76 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Chapter 6 — PID Application
Code Parameter Min. Max. Unit Default ID Note
P7.1.4

PID1 Process Unit 0 1297 40 = PA
41 = WC
42 = HG
43 = ft
44 = m
P7.1.5
PID1 Process Unit Min -99999.99 See Par ID 1300 Varies 0.00 1298
P7.1.6
PID1 Process Unit Max See Par ID 1298 99999.99 Varies 100.00 1300
P7.1.7
PID1 Process Unit Decimal 0 4 2 1302
P7.1.8

PID1 Error Inversion 0 1303 See Par ID 181
P7.1.9
PID1 Dead Band 0.00 99999.99 Varies 0.00 1304
P7.1.10
PID1 Dead Band Delay 0.00 320.00 s 0.00 1306
P7.1.11
PID1 Ramp Time 0.00 300.00 s 0.00 1311
Table 93. Monitor — P7.2
Code Parameter Min. Max. Unit Default ID Note
P7.2.1 FB PID1 Set Point 1 See Par ID 1298 See Par ID 1300 Varies 2542
P7.2.2 FB PID1 Set Point 2 See Par ID 1298 See Par ID 1300 Varies 2544
P7.2.3 FB PID1 Feedback 1 % 2550
P7.2.4 FB PID1 Feedback 2 % 2551
P7.2.5 FB PID1 Feedforward 1 % 2554
P7.2.6 FB PID1 Feedforward 2 % 2555
Setpoint
Table 94. Basic — P7.3.1
Code Parameter Min. Max. Unit Default ID Note
P7.3.1.1
PID1 Keypad Set Point 1 See Par ID 1298 See Par ID 1300 Varies 0.00 1307
P7.3.1.2
PID1 Keypad Set Point 2 See Par ID 1298 See Par ID 1300 Varies 0.00 1309
P7.3.1.3
PID1 Wake Up Action 0 2466 0 = Below Wake Up Level
1 = Above Wake Up Level
2 = Below Wake Up Level(PID ref.)
Wake up when below wakeup
level % set in Para ID 1318 or
1327 from PID Setpoint.
3 = Above Wake Up Level(PID ref.)
Wake up when above wakeup
level % set in Para ID 1318 or
1327 from PID Setpoint.
P7.3.1.4
PID1 Sleep Boost level -9999 9999 Varies 0 2660
P7.3.1.5
PID1 Sleep Boost Max Time 1 300 s 30 2661
ote:N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.
Input function is Level sensed.