EasyManua.ls Logo

Eaton PowerXL DH1 Series - Feedforward; Table 188. Basic - P8.5.1; Table 189. Feedforward 1 - P8.5.2; Table 190. Feedforward 2 − P8.5.3

Eaton PowerXL DH1 Series
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
120 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Chapter 7—Advanced application parameter
Feedforward
Table 188. Basic — P8.5.1
Code Parameter Min. Max. Unit Default ID Note
P8.5.1.1

PID2 Feedforward Func 0 1400 See Par ID 1330
P8.5.1.2
PID2 Feedforward Gain -1000.0 1000.0 % 100.0 1401
Table 189. Feedforward 1 — P8.5.2
Code Parameter Min. Max. Unit Default ID Note
P8.5.2.1

PID2 Feedforward 1 Source 0 1402 0 = Not Used
1 = AI1
2 = AI2
3 = Slot A: AI1
4 = Slot B: AI1
5 = FB Process Data Input 1
6 = FB Process Data Input 2
7 = FB Process Data Input 3
8 = FB Process Data Input 4
9 = FB Process Data Input 5
10 = FB Process Data Input 6
11 = FB Process Data Input 7
12 = FB Process Data Input 8
13 = PT100 Temperture
14 = PID1 Output
15 = SlotA PT100 Temp Channel 1
16 = SlotA PT100 Temp Channel 2
17 = SlotA PT100 Temp Channel 3
18 = SlotB PT100 Temp Channel 1
19 = SlotB PT100 Temp Channel 2
20 = SlotB PT100 Temp Channel 3
21 = FB PID2 Feedforward 1
22 = FB PID2 Feedforward 2
P8.5.2.2
PID2 Feedforward 1 Min -200.00 200.00 % 0.00 1403
P8.5.2.3
PID2 Feedforward 1 Max -200.00 200.00 % 100.00 1404
Table 190. Feedforward 2 − P8.5.3
Code Parameter Min. Max. Unit Default ID Note
P8.5.3.1

PID2 Feedforward 2 Source 0 1405 See Par ID 1402
P8.5.3.2
PID2 Feedforward 2 Min -200.00 200.00 % 0.00 1406
P8.5.3.3
PID2 Feedforward 2 Max -200.00 200.00 % 100.00 1407
Table 191. Fire Mode − P9
Code Parameter Min. Max. Unit Default ID Note
P9.1

Fire Mode Function 0 535 0 = Closing Contact
1 = Opening Contact
P9.2

Fire Mode Ref Select
Function
0 536 0 = Fire Mode Min Frequency
1 = Fire Mode Ref
2 = Fieldbus Ref
3 = AI1
4 = AI2
5 = AI1 + AI2
6 = PID1 Control Output
7 = PID2 Control Output
P9.3
Fire Mode Min Frequency See Par ID 101 See Par ID 102 Hz 15.00 537
P9.4
Fire Mode Freq Ref 1 0.0 100.0 % 75.0 565
P9.5
Fire Mode Freq Ref 2 0.0 100.0 % 100.0 564
P9.6 Fire Mode Test Enable 2443 See Par ID 1346
P9.7

Smoke Purge Frequency 0.0 100.0 % 50.0 554
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.

Table of Contents

Other manuals for Eaton PowerXL DH1 Series

Related product manuals