127POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Chapter 7—Advanced application parameter
Table 208 Basic Setting — P13.1, continued
Code Parameter Min. Max. Unit Default ID Note
P13.1.10 Default Page 0 628 0 = None
1 = Main Menu
2 = Multi-Monitor
3 = Favorite Menu
4 = Keypad Reference
P13.1.11 Timeout Time 0 65535 s 30 629
P13.1.12 Contrast Adjust 5 18 12 630
P13.1.13 Backlight Time 1 65535 min 10 631
P13.1.14 Fan Control 2 632 0 = Continuous
1 = Temperature
2 = Run Follow
3 = Calculate IGBT Temp
P13.1.15 Keypad ACK Timeout 200 5000 ms 200 633
P13.1.16 Keypad Retry Number 1 10 5 634
P13.1.17 Startup Wizard 0 626 0 = Yes
1 = No
P13.1.18
Jog Softkey Hidden 0 2412 See Par ID 1346
P13.1.19
Reverse Softkey Hidden 0 2413 See Par ID 1346
P13.1.20
Output Display Unit 45 2424 0 = %
1 = 1/min
2 = rpm
3 = ppm
4 = pps
5 = l/s
6 = l/min
7 = l/h
8 = kg/s
9 = kg/min
10 = kg/h
11 = m3/s
12 = m3/min
13 = m3/h
14 = m/s
15 = mbar
16 = bar
17 = Pa
18 = kPa
19 = mVS
20 = kW
21 = ºC
22 = GPM
23 = gal/s
24 = gal/min
25 = gal/h
26 = lb/s
27 = lb/min
28 = lb/h
29 = CFM
30 = ft3/s
31 = ft3/min
32 = ft3/h
33 = ft/s
34 = in wg
35 = ft wg
36 = PSI
37 = lb/in2
38 = HP
39 = °F
40 = PA
41 = WC
42 = HG
43 = ft
44 = m
45 = Hz
46 = strokes/min
P13.1.21
Output Display Unit Min -60000.00 See Par ID 2425 Varies 0.00 2460
P13.1.22
Output Display Unit Max See Par ID 2460 60000.00 Varies Varies 2425
P13.1.23 Keypad Lock Password 75
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.