Appendix A—Description of parameters
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Code Modbus ID Parameter Application RO/RW
P2.2.44 2119 Fire Mode Reverse 1,2,3 RW
Use this parameter for selecting an external input for enabling the motor to run in reverse when in fire
mode input is enabled. When the function is set for Normally Open and not in Fire mode the drive will run
as normal, when the function is set for Normally Closed and the Fire Mode input is enabled the motor will
spin in the counter clockwise direction. DigiIN:X indicates on-board terminal inputs, DigiIN:A:IOX:X indicates
optional board inputs in A slot and DigiIN:B:IOX:X indicates optional board inputs in B slot or Timer Channel
X. RO X Function allows for having an input turn on without having to hard wire it to the physical relay
output.
P2.2.45 224 Start Timer 1 2,3 RW
Use this parameter for selecting an external input for enabling the timer functions to begin
counting. When this function is set for Normally Open the drive will not start the Timer sequence. If the
function is set for Normally Close the Timer function will start. When assigned to an input the input active
will start the timer. Can be set to DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates
optional board inputs in A slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X.
RO X Function allows for having an input turn on without having to hard wire it to the physical relay output.
Closed contact: Timer1, Timer2 or Timer3 will be started.
P2.2.46 225 Start Timer 2 2,3 RW
Use this parameter for selecting an external input for enabling the timer functions to begin counting. When
this function is set for Normally Open the drive will not start the Timer sequence. If the function is set for
Normally Close the Timer function will start. When assigned to an input the input active will start the timer.
Can be set to DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates optional board inputs in
A slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X. RO X Function allows
for having an input turn on without having to hard wire it to the physical relay output. Closed contact:
Timer1,Timer2 or Timer3 will be started.
P2.2.47 226 Start Timer 3 2,3 RW
Use this parameter for selecting an external input for enabling the timer functions to begin counting. When
this function is set for Normally Open the drive will not start the Timer sequence. If the function is set for
Normally Close the Timer function will start. When assigned to an input the input active will start the timer.
Can be set to DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates optional board inputs in
A slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X. RO X Function allows for
having an input turn on without having to hard wire it to the physical relay output.
Closed contact: Timer1, Timer2 or Timer3 will be started.
P2.2.48 2801 OP Cont Interlock NO 1,2,3 RW
Output contactor interlock—normally open. The fault is active when the drive is in run mode and has a time
delay of 250ms for which the fault could occur. If the input contactor does not close within that time, the
drive will fault.
P2.2.49 2802 OP Cont Interlock NC 1,2,3 RW
Output contactor interlock—normally close. The fault is active when the drive is in run mode and has a time
delay of 250ms for which the fault could occur. If the input contactor does not close within that time, the
drive will fault.
P2.3.1 105 Preset Speed 1 1,2,3 RW
Use this parameter to set the Preset Frequency 1.
P2.3.2 106 Preset Speed 2 1,2,3 RW
Use this parameter to set the Preset Frequency 2.
P2.3.3 118 Preset Speed 3 1,2,3 RW
Use this parameter to set the Preset Frequency 3.
P2.3.4 119 Preset Speed 4 1,2,3 RW
Use this parameter to set the Preset Frequency 4.
P2.3.5 120 Preset Speed 5 1,2,3 RW
Use this parameter to set the Preset Frequency 5.
P2.3.6 121 Preset Speed 6 1,2,3 RW
Use this parameter to set the Preset Frequency 6.
P2.3.7 122 Preset Speed 7 1,2,3 RW
Use this parameter to set the Preset Frequency 7.
P2.3.8 117 Jog Reference 1,2,3 RW
Use this parameter to set the jogging speed set point, this speed is selected with the digital input programmed
for Jogging speed. When enabled the drive starts and ramps to this speed, input removed drive stops.
This parameter’s value is automatically limited between minimum and maximum frequency.