Chapter 5—Basic application
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Table 42. Drive — P6.2, continued
Code Parameter Min. Max. Unit Default ID Note
P6.1.18
Preheat Control Source 31 2160 35 = SlotA Max PT100 Temp
36 = SlotB PT100 Temp Channel 1
37 = SlotB PT100 Temp Channel 2
38 = SlotB PT100 Temp Channel 3
39 = SlotB Max PT100 Temp
40 = SlotA and SlotB Max PT100
Temp
P6.1.19
Preheat Enter Temp 0.0 19.9 °C 10.0 2161
P6.1.20
Preheat Quit Temp 20.0 40.0 °C 20.0 2162
P6.1.21
Preheat Output Volt 0.0 20.0 % 2.0 2163
Table 43. Communication — P6.3
Code Parameter Min. Max. Unit Default ID Note
P6.3.1

Fieldbus Fault Response 2 334 0 = No Action
1 = Warning
2 = Fault
3 = Fault, Coast
4 = Warning, Coast
P6.3.2

OPTCard Fault Response 2 335 See Par ID 308
P6.3.3

IP Address Confliction Resp 1 1678 See Par ID 308
P6.3.4

Keypad Comm Fault
Response
2 2157 See Par ID 308
Table 44. Auto Restart — P6.4
Code Parameter Min. Max. Unit Default ID Note
P6.4.1
AR Wait Time 1.00 300.00 s 1.00 321
P6.4.2
AR Trail Time 0.00 600.00 s 30.00 322
P6.4.3
AR Start Function 0 323 0 = Flying Start
1 = Ramp
P6.4.4
Undervoltage Attempts 0 10 1 324
P6.4.5
OverVoltage Attempts 0 10 1 325
P6.4.6
OverCurrent Attempts 0 3 1 326
P6.4.7
4mA Fault Attempts 0 10 1 327
P6.4.8
Motor Temp Fault Attempts 0 10 1 329
P6.4.9
External Fault Attempts 0 10 0 328
P6.4.10
Underload Attempts 0 10 1 336
P6.4.11
OP Cont Interlock Attempts 0 10 0 2803
Table 45. Fire Mode — P9
Code Parameter Min. Max. Unit Default ID Note
P9.1

Fire Mode Function 0 535 0 = Closing Contact
1 = Opening Contact
P9.2

Fire Mode Ref Select
Function
0 536 0 = Fire Mode Min Frequency
1 = Fire Mode Ref
2 = Fieldbus Ref
3 = AI1
4 = AI2
5 = AI1 + AI2
P9.3
Fire Mode Min Frequency See Par ID 101 See Par ID 102 Hz 15.00 537
P9.4
Fire Mode Freq Ref 1 0.0 100.0 % 75.0 565
P9.5
Fire Mode Freq Ref 2 0.0 100.0 % 100.0 564
P9.6 Fire Mode Test Enable 2443 See Par ID 1679
otes:N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.