Step 5Standard Parameter List
PowerXL DH1 Series Variable Frequency Drives MN040039EN—April 2018 www.eaton.com 17
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Parameters
Table 16. Operate Mode—O
Code Parameter Min. Max. Unit Default ID Note
O1 Output Frequency Hz 0 1
O2 Freq Reference Hz 0 24
O3 Motor Speed rpm 0 2
O4 Motor Current A 0 3
O5 Motor Torque % 0 4
O6 Motor Power % 0 5
O7 Motor Voltage V 0 6
O8 DC-link Voltage V 0 7
O9 Unit Temperature °C 0 8
O10 Motor Temperature % 0 9
R11
2
Keypad Reference PAR ID 101 PAR ID 102 Hz 0 141
Table 17. Basic Parameters—P1
Code Parameter Min. Max. Unit Default ID Note
P1.1
12
Min Frequency 0.00 See Par ID 102 Hz 0.00 101
P1.2
12
Max Frequency See Par ID 101 400.00 Hz MaxFreqMFG 102
P1.3
2
Accel Time 1 0.1 3000.0 s 20.0 103
P1.4
2
Decel Time 1 0.1 3000.0 s 20.0 104
P1.5
1
Motor Nom Current DriveNomCurr
CT*1/10
DriveNomCurr
CT*2
A DriveNomCurrCT 486
P1.6
1
Motor Nom Speed 300 20000 rpm MotorNomSpeed
MFG
489
P1.7
1
Motor PF 0.30 1.00 0.85 490
P1.8
1
Motor Nom Voltage 180 690 V MotorNomVoltMFG 487
P1.9
1
Motor Nom Frequency 8.00 400.00 Hz MotorNomFreqMFG 488
P1.10
12
HOA Source 0 2465 0 = I/O Terminal/Keypad/Fieldbus
1 = Keypad
2 = IO Terminal
3 = Fieldbus
P1.11
2
Hand Control Place 0 1695 0 = Keypad
1 = I/O Terminal Start 1
2 = I/O Terminal Start 2
3 = Fieldbus