Step 5Standard Parameter List
18 PowerXL DH1 Series Variable Frequency Drives MN040039EN—April 2018 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Inputs
P1.12
12
Hand Reference 6 136 0 = AI1
1 = AI2
2 = Slot A: AI1
3 = Slot B: AI1
6 = Keypad
7 = Fieldbus Ref
9 = Max Frequency
10 = AI1 + AI2
11 = AI1 - AI2
12 = AI2 - AI1
13 = AI1 * AI2
14 = AI1 or AI2
15 = MIN(AI1,AI2)
16 = MAX(AI1,AI2)
P1.13
2
Auto 1 Control Place 0 135 0 = I/O Terminal Start 1
1 = Fieldbus
2 = I/O Terminal Start 2
3 = Keypad
P1.14
12
Auto 1 Reference 1 137 See Par ID 136
P1.15
2
Auto 2 Control Place 1 138 See Par ID 135
P1.16
12
Auto 2 Reference 7 139 See Par ID 136
Table 17. Basic Parameters—P1, continued
Code Parameter Min. Max. Unit Default ID Note
Table 18. Basic Setting—P2.1
Code Parameter Min. Max. Unit Default ID Note
P2.1.4
2
AI Ref Scale Min Value 0.00 See Par ID 145 Hz 0.00 144
P2.1.5
2
AI Ref Scale Max Value See Par ID 144 400.00 Hz 0.00 145
Table 19. Digital Input—P2.2
Code Parameter Min. Max. Unit Default ID Note
P2.2.1
12
IO Terminal 1 Start Stop
Logic
0 143 0 = Forward - Reverse
1 = Start - Reverse
2 = Start - Enable
3 = Start Pulse - Stop Pulse