Step 5—Standard Parameter List
PowerXL DH1 Series Variable Frequency Drives MN040039EN—April 2018 www.eaton.com 21
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Table 20. AI1 Settings—P2.4
Code Parameter Min. Max. Unit Default ID Note
P2.4.1 AI1 Mode 1 222 0 = 0–20 mA
1 = 0–10 V
P2.4.2
2
AI1 Signal Range 0 175 0 = 0–100%/0–20 mA/0–10 V
1 = 20–100%/4–20 mA/2–10 V
2 = Customized
P2.4.3
2
AI1 Custom Min 0.00 See Par ID 177 % 0.00 176
P2.4.4
2
AI1 Custom Max See Par ID 176 100.00 % 100.00 177
P2.4.5
2
AI1 Filter Time 0.00 10.00 s 0.10 174
P2.4.6
2
AI1 Signal Invert 0 181 0 = Not Inverted
1 = Inverted
Table 21. AI2 Settings—P2.5
Code Parameter Min. Max. Unit Default ID Note
P2.5.1 AI2 Mode 0 223 0 = 0–20 mA
1 = 0–10 V
2 = -10– +10 V
P2.5.2
2
AI2 Signal Range 1 183 0 = 0–100%/0–20 mA/
0 = 0–10 V/-10–10 V
1 = 20–100%/4–20 mA/
1 = 2–10 V/-6–10 V
2 = Customized
P2.5.3
2
AI2 Custom Min 0.00 See Par ID 185 % 0.00 184
P2.5.4
2
AI2 Custom Max See Par ID 184 100.00 % 100.00 185
P2.5.5
2
AI2 Filter Time 0.00 10.00 s 0.10 182
P2.5.6
2
AI2 Signal Invert 0 189 See Par ID 181
Table 22. Digital Output—P3.1
Code Parameter Min. Max. Unit Default ID Note
P3.1.1
2
DO1 Function 1 151 0 = Not Used
1 = Ready
2 = Run
3 = Fault
4 = Fault Invert
5 = Warning
6 = Reversed
7 = At Speed
8 = Zero Frequency
9 = Freq Limit 1 Superv
10 = Freq Limit 2 Superv
13 = OverHeat Fault
14 = OverCurrent Regular
15 = OverVoltage Regular
16 = UnderVoltage Regular
17 = 4mA Ref Fault/Warning
20 = Torq Limit Superv
21 = Ref Limit Superv
22 = Control from I/O
23 = Un-Requested Rotation
23 = Direction
24 = Thermistor Fault Output