Step 5Standard Parameter List
22 PowerXL DH1 Series Variable Frequency Drives MN040039EN—April 2018 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Table 22. Digital Output—P3.1, continued
Code Parameter Min. Max. Unit Default ID Note
P3.1.1
2
,
continued
DO1 Function 1 151 25 = Fire Mode
26 = In Bypass Mode
27 = Ext Fault/Warning
28 = Auto Control
29 = Jog Speed Select
30 = Motor Therm Protection
31 = FB Digital Input 1
32 = FB Digital Input 2
33 = FB Digital Input 3
34 = FB Digital Input 4
40 = Power Limit Superv
41 = Temp Limit Superv
42 = Analog Input Superv
51 = Motor Current 1 Supv
52 = Motor Current 2 Supv
53 = Second AI Limit Supv
54 = DC Charge Switch Close
55 = Preheat Active
56 = Cold Weather Active
58 = 2th Stage Ramp Frequency
58 = Active
59 = STO Fault Output
60 = Run Bypass/Drive
61 = Bypass Overload
62 = Bypass Run
P3.1.2
2
RO1 Function 62 152 See Par ID 151
P3.1.3
2
RO1 On Delay 0.0 320.0 s 0.0 2112
P3.1.4
2
RO1 Off Delay 0.0 320.0 s 0.0 2113
P3.1.5
2
RO2 Function 2 153 See Par ID 151
P3.1.6
2
RO2 On Delay 0.0 320.0 s 0.0 2114
P3.1.7
2
RO2 Off Delay 0.0 320.0 s 0.0 2115
P3.1.8
2
RO3 Function 3 538 See Par ID 151
P3.1.9
2
RO3 On Delay 0.0 320.0 s 0.0 2116
P3.1.10
2
RO3 Off Delay 0.0 320.0 s 0.0 2117
P3.1.11
2
RO3 Reverse 0 2118 0 = No
1 = Yes
P3.1.12
2
Virtual RO1 Function 0 2463 See Par ID 151
P3.1.13
2
Virtual RO2 Function 0 2464 See Par ID 151
Table 23. Supervisions—P3.2
Code Parameter Min. Max. Unit Default ID Note
P3.2.1
2
Freq Limit 1 Supv 0 154 0 = No Limit
1 = Low Limit Superv
2 = High Limit Superv
P3.2.2
2
Freq Limit 1 Supv Val 0.00 See Par ID 102 Hz 0.00 155
P3.2.3
2
Freq Limit 1 Supv Hyst 0.10 1.00 Hz 0.10 2200
P3.2.4
2
Freq Limit 2 Supv 0 157 See Par ID 154
P3.2.5
2
Freq Limit 2 Supv Val 0.00 See Par ID 102 Hz 0.00 158
P3.2.6
2
Freq Limit 2 Supv Hyst 0.10 1.00 Hz 0.10 2201
P3.2.7
2
Torque Limit Supv 0 159 See Par ID 154