Step 5Standard Parameter List
24 PowerXL DH1 Series Variable Frequency Drives MN040039EN—April 2018 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Table 24. Analog Output 1—P3.3
Code Parameter Min. Max. Unit Default ID Note
P3.3.1
2
AO1 Mode 0 227 See Par ID 222
P3.3.2
2
AO1 Function 1 146 0 = Not Used
1 = Output Frequency
2 = Freq Reference
3 = Motor Speed (0–Nom)
4 = Motor Current (0–Nom)
5 = Motor Torque (0–Nom)
6 = Motor Power (0–Nom)
7 = Motor Voltage (0–Nom)
8 = DC-Bus Voltage
19 = AI1
20 = AI2
21 = Output Freq (-2-+2N)
22 = Motor Torque (-2-+2N)
23 = Motor Power (-2-+2N)
24 = PT100 Temperature
33 = SlotA PT100 Temp Channel 1
34 = SlotA PT100 Temp Channel 2
35 = SlotA PT100 Temp Channel 3
36 = SlotB PT100 Temp Channel 1
37 = SlotB PT100 Temp Channel 2
38 = SlotB PT100 Temp Channel 3
39 = User Defined Output
40 = Motor Current (-2-+2N)
P3.3.3
2
AO1 Minimum 1 149 0 = 0 V / 0 mA
1 = 2 V / 4 mA
P3.3.4
2
AO1 Filter Time 0.00 10.00 s 1.00 147
P3.3.5
2
AO1 Scale 10 1000 % 100 150
P3.3.6
2
AO1 Inversion 0 148 See Par ID 181
P3.3.7
2
AO1 Offset -100.00 100.00 % 0.00 173
Table 25. Analog Output 2—P3.4
Code Parameter Min. Max. Unit Default ID Note
P3.4.1
2
AO2 Mode 0 228 See Par ID 222
P3.4.2
2
AO2 Function 4 229 See Par ID 146
P3.4.3
2
AO2 Minimum 1 232 See Par ID 149
P3.4.4
2
AO2 Filter Time 0.00 10.00 s 1.00 230
P3.4.5
2
AO2 Scale 10 1000 % 100 233
P3.4.6
2
AO2 Inversion 0 231 See Par ID 181
P3.4.7
2
AO2 Offset -100.00 100.00 % 0.00 234