Step 5—Standard Parameter List
PowerXL DH1 Series Variable Frequency Drives MN040039EN—April 2018 www.eaton.com 25
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Drive Control
Table 26. Basic Setting—P4.1
Code Parameter Min. Max. Unit Default ID Note
P4.1.1
2
Keypad Reference See Par ID 101 See Par ID 102 Hz 0.00 141
P4.1.2
2
Keypad Direction 0 116 0 = Forward
1 = Reverse
P4.1.3
2
Keypad Stop 1 114 0 = Enabled-Keypad Operation
1 = Always Enabled
P4.1.4
2
Hand Key Enable 0 1724 0 = Enabled
1 = Disabled
P4.1.5
1
Reverse Enable 0 1679 0 = Disabled
1 = Enabled
P4.1.6 Change PhaseSequence
Motor
0 2515 0 = Change Disable
1 = Change Enable
P4.1.7
2
Power Up HOA Select 0 1685 0 = Hold Last
1 = Hand Control
2 = Auto control
3 = Off
P4.1.9
2
Run Delay Time 0 32500 s 0 2423
P4.1.10
2
Start Mode 0 252 0 = Ramp
1 = Flying Start
P4.1.11
2
Stop Mode 0 253 0 = Coasting
1 = Ramp
P4.1.12
2
Ramp 1 Shape 0.0 10.0 s 0.0 247
P4.1.13
2
Ramp 2 Shape 0.0 10.0 s 0.0 248
P4.1.14
2
Accel Time 2 0.1 3000.0 s 10.0 249
P4.1.15
2
Decel Time 2 0.1 3000.0 s 10.0 250
P4.1.16
2
Power Loss Function 0 267 See Par ID 1679
P4.1.17
2
Power Loss Time 0.3 5.0 s 2.0 268
P4.1.18
1
2
2nd Stage Ramp Frequency See Par ID 101 See Par ID 102 Hz 30.00 2444
Table 27. Brake—P4.2
Code Parameter Min. Max. Unit Default ID Note
P4.2.1
1
2
DC-Brake Current DriveNomCurr
CT*15/100
DriveNomCurr
CT*15/10
A DriveNomCurr
CT*1/2
254
P4.2.2
1
2
Start DC-Brake Time 0.00 600.00 s 0.00 263
P4.2.3
1
2
Stop DC-Brake Frequency 0.10 10.00 Hz 1.50 262
P4.2.4
1
2
Stop DC-Brake Time 0.00 600.00 s 0.00 255
P4.2.5
1
2
Brake Chopper Define 0 251 0 = Disabled
1 = B(Run) T(Rdy)
2 = External
3 = B(Rdy) T(Rdy)
4 = B(Run) T(No)
P4.2.6
1
2
Flux Brake 0 266 0 = Off
1 = On
P4.2.7
1
2
Flux Brake Current ActiveMotor
NomCurr*1/10
See Par ID 107 A ActiveMotorNom
Curr*1/2
265