Step 5—Standard Parameter List
26 PowerXL DH1 Series Variable Frequency Drives MN040039EN—April 2018 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Motor Control
Table 28. Skip Frequency—P4.3
Code Parameter Min. Max. Unit Default ID Note
P4.3.1
2
Skip Range Ramp Factor 0.1 10.0 1.0 264
P4.3.2
2
Skip F1 Low Limit 0.00 See Par ID 257 Hz 0.00 256
P4.3.3
2
Skip F1 High Limit See Par ID 256 400.00 Hz 0.00 257
P4.3.4
2
Skip F2 Low Limit 0.00 See Par ID 259 Hz 0.00 258
P4.3.5
2
Skip F2 High Limit See Par ID 258 400.00 Hz 0.00 259
P4.3.6
2
Skip F3 Low Limit 0.00 See Par ID 261 Hz 0.00 260
P4.3.7
2
Skip F3 High Limit See Par ID 260 400.00 Hz 0.00 261
Table 29. Energy Savings Calc—P4.4
Code Parameter Min. Max. Unit Default ID Note
P4.4.1
2
Currency 0 2122 0 = $
1 = £
2 = €
3 = ¥
4 = Rs
5 = R$
6 = Fr
7 = kr
P4.4.2
2
Energy Cost Varies 0.00 2123
P4.4.3
2
Data Type 0 2124 0 = Cumulative
1 = Daily Avg
2 = Weekly Avg
3 = Monthly Avg
4 = Yearly Avg
P4.4.4 Energy Savings Reset 2125 0 = Not Reset
1 = Reset
Table 30. Basic Setting—P5.1
Code Parameter Min. Max. Unit Default ID Note
P5.1.1
1
2
Motor Control Mode 0 287 0 = Freq Control
1 = Speed Control
P5.1.2
1
Current Limit DriveNomCurr
CT*1/10
DriveNomCurr
CT*2
A DriveNomCurrCT*2 107
P5.1.3
1
2
V/Hz Optimization 0 109 See Par ID 1679
P5.1.4
1
2
V/Hz Ratio 3 108 0 = Linear
1 = Squared
2 = Programmable
3 = Linear + Flux Optimization
P5.1.5
1
2
Field Weakening Point 8.00 400.00 Hz FieldWeakPointMFG 289
P5.1.6
1
2
Voltage at FWP 10.00 200.00 % 100.00 290
P5.1.7
1
2
V/Hz Mid Frequency 0.00 See Par ID 289 Hz VHzCurveMidFreq
MFG
291
P5.1.8
1
2
V/Hz Mid Voltage 0.00 100.00 % 100.00 292
P5.1.9
1
2
Zero Frequency Voltage 0.00 40.00 % 0.00 293