Step 5Standard Parameter List
PowerXL DH1 Series Variable Frequency Drives MN040039EN—April 2018 www.eaton.com 33
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
P12.2.9
2
Standard Status Word Bit0
Function Select
1 2415 0 = Not Used
1 = Ready
2 = Run
3 = Fault
4 = Fault Invert
5 = Warning
6 = Reversed
7 = At Speed
8 = Zero Frequency
9 = Freq Limit 1 Superv
10 = Freq Limit 2 Superv
13 = OverHeat Fault
14 = OverCurrent Regular
15 = OverVoltage Regular
16 = UnderVoltage Regular
17 = 4mA Ref Fault/Warning
20 = Torq Limit Superv
21 = Ref Limit Superv
22 = Control from I/O
23 = Un-Requested Rotation
23 = Direction
24 = Thermistor Fault Output
25 = Fire Mode
26 = In Bypass Mode
27 = Ext Fault/Warning
28 = Auto Control
29 = Jog Speed Select
30 = Motor Therm Protection
31 = FB Digital Input 1
32 = FB Digital Input 2
33 = FB Digital Input 3
34 = FB Digital Input 4
40 = Power Limit Superv
41 = Temp Limit Superv
42 = Analog Input Superv
51 = Motor Current 1 Supv
52 = Motor Current 2 Supv
53 = Second AI Limit Supv
54 = DC Charge Switch Close
55 = Preheat Active
56 = Cold Weather Active
58 = 2th Stage Ramp Frequency
58 = Active
59 = STO Fault Output
60 = Run Bypass/Drive
61 = Bypass Overload
62 = Bypass Run
P12.2.10
2
Standard Status Word Bit1
Function Select
2 2416 See Par ID 2415
P12.2.11
2
Standard Status Word Bit2
Function Select
3 2417 See Par ID 2415
P12.2.12
2
Standard Status Word Bit3
Function Select
4 2418 See Par ID 2415
P12.2.13
2
Standard Status Word Bit4
Function Select
5 2419 See Par ID 2415
Table 38. FB Process Data Output Sel—P12.2, continued
Code Parameter Min. Max. Unit Default ID Note