138
Hardware specifi cation
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Table 170. Bit definitions for status instance attribute of identity object
Bits Called Definitions
0 Owned TRUE indicates the device (or an object within the device) has an owner.
Within the Master/Slave paradigm the setting of this bit means that the
Predefined Master/Slave Connection Set has been allocated to a master.
1 Reserved Reserved, shall be 0
2 Configured TRUE indicates the application of the device has been configured to do
something different than the “out-of-box” default. This shall not include
configuration of the communications.
3 Reserved Reserved, shall be 0
4–7 Extended device status Vendor-specific or as defined by Table 179.
8Not used
9Not used
10 Not used
11 Not used
12–15 Extended device status 2 Reserved—(shall be 0)
Table 171. Values for extended device status field
(Bits 4–7) in status instance attribute
Value Description
0 Self-Testing or Unknown
2 At least one faulted I/O connection
3 No I/O connections established
6 At least one I/O connection in run mode
7 At least one I/O connection established, all in idle mode