63
Appendix B—Installation guidelines
POWERXL SERIES VFDS MN040060EN—September 2020 www.eaton.com
Table 34. Input current scaling (continued).
Output rating Input rating
Max rating Option 1 Option 2 Option 3 Max rating Option 1 Option 2 Option 3
Input
voltage
Frame
size
Drive
catalog
number
CT/I
H
cur-
rent
amps
VT/I
L
cur-
rent
amps
CT/I
H
cur-
rent
amps
VT/I
L
cur-
rent
amps
CT/I
H
cur-
rent
amps
VT/I
L
cur-
rent
amps
CT/I
H
cur-
rent
amps
VT/I
L
cur-
rent
amps
CT/I
H
cur-
rent
amps
VT/I
L
cur-
rent
amps
CT/I
H
cur-
rent
amps
VT/I
L
cur-
rent
amps
CT/I
H
cur-
rent
amps
VT/I
L
cur-
rent
amps
CT/I
H
cur-
rent
amps
VT/I
L
cur-
rent
amps
380 Vac
to 480
Vac
50/60 Hz
3-phase
FR1 DM1-
341D5…
1.5 2.2 1.1 1.5 0.9 1.1 0.7 0.9 1.8 2.6 1.5 1.8 1.2 1.5 1 1.2
DM1-
342D2…
2.2 4.3 1.5 2.2 1.1 1.5 0.9 1.1 2.6 5.2 1.8 2.6 1.5 1.8 1.2 1.5
DM1-
344D3…
4.3 5.6 2.2 4.3 1.5 2.2 1.1 1.5 5.2 6.7 2.6 5.2 1.8 2.6 1.5 1.8
DM1-
345D6…
5.6 7.6 4.3 5.6 2.2 4.3 1.5 2.2 6.7 9.1 5.2 6.7 2.6 5.2 1.8 2.6
FR2 DM1-
347D6…
7.6 12 5.6 7.6 4.3 5.6 2.2 4.3 9.1 14.4 6.7 9.1 5.2 6.7 2.6 5.2
DM1-
34012…
12 16 7.6 12 5.6 7.6 4.3 5.6 14.4 19.2 9.1 14.4 6.7 9.1 5.2 6.7
DM1-
34016…
16 23 12 16 7.6 12 5.6 7.6 19.2 2 7.6 14.4 19.2 9.1 14.4 6.7 9.1
FR3 DM1-
34023..
23 31 16 23 12 16 7.6 12 26.5 35.7 19.2 27.6 14.4 19.2 9.1 14.4
FR4 DM1-
34 031…
31 38 23 31 16 23 12 16 35.7 43.7 26.5 35.7 19.2 2 7.6 14.4 19.2
DM1-
34038…
38 46 31 38 23 31 16 23 43.7 52.9 35.7 43.7 26.5 35.7 19.2 27.6
525 Vac
to 600
Vac
50/60 Hz
3-Phase
FR2 DM1-
354D5…
4.5 7.5 2.7 4.5 1.7 2.7 1.4 1.7
DM1-
357D5…
7.5 10 4.5 7.5 2.7 4.5 1.7 2.7
DM1-
35010…
10 13.5 7.5 10 4.5 7.5 2.7 4.5
FR3 DM1-
35013…
13.5 18 10 13.5 7.5 10 4.5 7.5
FR4 DM1-
35018…
18 22 13.5 18 10 13.5 7.5 10
DM1-
35022…
22 27 18 22 13.5 18 10 13.5