51
Appendix B—Installation guidelines
POWERXL SERIES VFDS MN040060EN—September 2020 www.eaton.com
Table 28. UL cable and fuse sizes (continued).
Output rating Input rating UL application
Input
voltage
Frame
size
Drive
catalog
number
CT/I
H
current
amps
VT/I
L
current
amps
CT/I
H
current
amps
VT/I
L
current
amps
Recom-
mended
fuse
(Class
J, T, CF
or CC)
(max
rating)
100
kAIC①
Recom-
mended
miniature
inverse-
time
molded-
case
circuit
breaker
(max
rating)
10/14
kAIC①
Recom-
mended
Type E CMC
(max rating)
65 kAIC②
Recom-
mended
inverse-
time
molded-
case
circuit
breaker
(max
rating)
100 kAIC
(open type
only for
3-phase)①
NEC
wire
size
line
and
motor
AWG
NEC
wire
size
ground
AWG
Term-
inal
size
line
and
motor
AWG
Term-
inal
size
ground
AWG
380 Vac
to 480
Vac
50/60
Hz
3-Phase
(cont.)
FR4 DM1-
34 031…
31 38 35.7 43.7 70 \ XTPR050DC1 +
XTPAXLSAD or
PKZM4-50 +
BK50/3-PKZ4-E
EGC3070FFG 6 8 20-2 8-6
DM1-
34038…
38 46 43.7 52.9 80 \ XTPR058DC1 +
XTPAXLSAD or
PKZM4-58 +
BK50/3-PKZ4-E
EGC3080FFG 4 8 20-2 8-6
525 Vac
to 600
Vac
50/60
Hz
3-Phase
FR2 DM1-
354D5…
DM1-
357D5…
DM1-
35010…
FR3 DM1-
35013…
FR4 DM1-
35018…
DM1-
35022…
Notes:
① Can be any UL listed types with the same ratings.
② Due to UL listing, only can be below Eaton types.