149
Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Table 54. Monitor (Cont.).
M3.2
b
CO2 savings
ID 1818
Minimum value:
mt/y
Maximum value:
mt/y
Default value:
0.000 mt/y
Description:
Displays the CO2 savings of the drive compared to linear V/f curve.
M4 - FB monitor menu.
M4.1
Control board DIDO status
ID 2209
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
Bit 0 = DI1_Status;
Bit 1 = DI2_Status;
Bit 2 = DI3_Status;
Bit 3 = DI4_Status;
Bit 4 = RO1_Status;
Bit 5 = RO2_Status;
Bit 6 = SlotA with board;
Bit 7 = Virtual_RO1_Status; or
Bit 8 = Virtual_RO2_Status.
Description:
Control board digital input and relay output status provides the status of inputs and outputs on the control board.
M4.2
Application status word
ID 29
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
Bit 0 = MC_Ready;
Bit 1 = MC_Run;
Bit 2 = MC_Fault or Fault Trip;
Bit 3 = FB_Ref_Active;
Bit 4 = MC_Stopping;
Bit 5 = MC_Reverse;
Bit 6 = MC_Warning or AR-Fault;
Bit 7 = MC_ZeroSpeed;
Bit 8 = IO control indicator;
Bit 9 = Panel control indicator;
Bit 10 = Panel fieldbus control indicator;
Bit 11 = MC_DC_Brake;
Bit 12 = Run enable;
Bit 13 = Run bypass;
Bit 14 = External brake control; or
Bit 15 = In bypass mode.
Description:
Application status word will provide additional status indication of the health of the drive.
M4.3
Standard status word
ID 2414
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
Bit 0 = See STD status word B0 Sel (default = ready);
Bit 1 = See STD status word B1 Sel (default = run);
Bit 2 = See STD status word B2 Sel (default = fault);
Bit 3 = See STD status word B3 Sel (default = fault Invert);
Bit 4 = See STD status word B4 Sel (default = warning);
Bit 5 = See STD status word B5 Sel (default = reversed);
Bit 6 = See STD status word B6 Sel (default = at speed);
Bit 7 = See STD status word B7 Sel (default = zero frequency); or
Bit 8 - 15 = Not used.
Description:
Standard status word is defined based of the parameter setting in the fieldbus process data group, define the first 8 bits of this status
word. The options for these bits are based off the standard relay functions.
M4.4
FB PI setpoint 1
ID 2542
Minimum value:
Varies
Maximum value:
PID1_ProcessUnit Max
Default value:
Varies.
Description:
PID setpoint 1 value from fieldbus.
M4.5
FB PI setpoint 2
ID 2544
Minimum value:
PID1_ProcessUnitMin
Maximum value:
PID1_ProcessUnit Max
Default value:
Varies.
Description:
PID setpoint 2 value from fieldbus.