4 Accessories
4.7 Device-specific accessories for devices with an IP20 degree of protection
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com 101
Figure 69: Block diagram DXC-EXT-2RO
Parameter definition
The K1 relay output’s function can be configured using parameter P-18
(default setting = 1: RUN). Meanwhile, the new K2 relay output’s function
can be configured using parameter P-25 (default setting = Analog output
AO1).
Depending on the type of load, we recommend the use of a
suppressor circuit when using the relay outputs ( gure 53,
page 80).
Parameter P-25 must be set to a value between 0 and 7 in order
for the output to function as a digital output.
If the parameter is set to a value greater than 7, relay output K2
will not work properly.
For detailed instructions on how to install the module, please
refer to instruction leaflet IL04012015Z.
NOTICE
Internal relay K1 is connected to the expansion module,
meaning it can only conduct a relatively low current ( 1A).
DANGER
Dangerous voltage!
Expansion module DXC-EXT-2RO1AO must not be placed into
operation until all mounting and installation work has been
completed (plugged in and connected to the DC1-S variable
frequency drive’s control signal terminals). Any other use will be
considered to be an inappropriate use.
2
DI1
3
DI2
4
DI3
1
5
+10 V
< 20 mA
6 7
0 V
8 9 10 11
1DC1 2 3 4 5 6 8 9 10 11
P-18 = 1
RUN
P-25
7
AI
0 ... +10 V
+24 V
< 100 mA
f-Soll
K2 K1
250 V AC
220 V DC
≦ 1 A
4.7 kΩ