4 Accessories
4.7 Device-specific accessories for devices with an IP20 degree of protection
104 DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com
Parameter definition
P-18 = 1: READY, variable frequency drive ready for operation
Typical operating mode (DXC-EXT-2RO1AO control signal terminals):
12/13 closed
There is an enable signal for operation (FWD),
READY and RUN messages: Green indicator light, for example
10/11 closed Error message (not READY):
Red indicator light, for example
P-18 can also be used to select other operating messages for
the DC1-S… variable frequency drive’s internal relay (RO1)
( “Parameter Manual” MN040022EN).