EasyManua.ls Logo

Eaton PowerXL - Page 119

Eaton PowerXL
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Operation
5.5 Commissioning with control signal terminals (default settings)
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com 115
5.5.2.2 t-Boost (P-33)
Once you have determined the correct value for V-Boost, you will need to
adjust the t-Boost (P-33) parameter. This can be done in large increments of
approximately 50 % until you are close to the required value.
The ideal duration is approx. 1 to 2 seconds longer than the duration required
in order to bring the motor to full speed.
Make sure that the correct value for V-Boost (P-11), as determined with
the procedure described in section 5.5.2.1, “V-Boost (P-11)”, is set.
Select a speed reference value that is lower than the maximum value.
This will make it possible to recognize the end of t-Boost, as the motor
will then decelerate to the set speed.
Start the drive. Press the OK button as many times as necessary until
the current, “A…xxx”, is displayed.
Check whether the motor starts with a rising voltage.
After the motor starts, the current will increase. As soon as the motor
reaches its full speed, the current will decrease rapidly. If the time set
with t-Boost is too long, the voltage at this point will still be relatively
low and the motor will be rotating with a high current.
Determine the time between the moment the motor starts and the
moment it reaches full speed.
Reduce the t-Boost value and repeat the test.
If the motor reaches its full speed before t-Boost elapses, keep
reducing the value of t-Boost and repeating the test.
It is not uncommon for the O-I and It.trp faults to occur during this
testing phase. If the device trips, wait at least 30 seconds before running
the test again.
If the value of t-Boost is too large, the motor will continue to run with a
reduced voltage and, accordingly, a higher current for some time after
starting. If this occurs, reduce the value of t-Boost (P-33).
5.5.2.3 f-Boost (P-32)
In most cases, f-Boost (P-32) will be equal to the rated motor frequency
(P-09) and will not need to be adjusted during commissioning.
If necessary, however, the value can be changed.

Table of Contents

Related product manuals