6 Parameter structure
6.4 Control signal terminals
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com 125
Select BUS REF/f-Fix1 Used to select between the setpoint value from the bus and fixed frequency 1
(f-Fix1), which is set with P-20
Low = Setpoint value from bus
High = f-Fix1
Select BUS REF/f-Fix4
Used to select between the setpoint value from the bus and fixed frequency 4
(f-Fix4), which is set with P-23
Low = Setpoint value from bus
High = f-Fix4
Select DIG REF/AI1 REF
Used to select between the digital speed reference value, set with the keypad or
with the UP and DOWN commands, and analog setpoint value AI1 REF
(terminal 6)
Low = digital setpoint value
•High = AI1
Select DIG REF/f-Fix1
Used to select between the digital speed reference value, set with the keypad or
with the UP and DOWN commands, and fixed frequency 1 (f-Fix1) set with P-20.
Low = digital setpoint value
High = f-Fix1
Select DIG REF/f-Fix4
Used to select between the digital speed reference value (set with the keypad or
with the UP and DOWN commands) and fixed frequency 4 (f-Fix4), which is set
with P-23
Low = digital setpoint value
High = f-Fix4
Select f-Fix Bit0/f-Fix Bit1
Used to select a fixed frequency with digital commands
Fixed frequencies f-Fix1, …, f-Fix4 are defined with parameters P-20 up to P-23.
0 = Low
1 = High
Select f-Fix/BUS REF
Used to select between a fixed frequency and the setpoint value from the bus.
Low = Fixed frequency
High = Setpoint value from bus
Select f-Fix/DIG REF
Used to select between a fixed frequency and the digital setpoint value, which is
set with the keypad or with the UP and DOWN commands.
Low = Fixed frequency
High = Digital setpoint value
Select f-Fix/f-max
Used to select between a fixed frequency and the maximum speed set with P-01.
Low = Fixed frequency
High = maximum speed
The fixed frequency itself is selected with the Select f-Fix Bit0 or Select f-Fix Bit1
commands.
Select f-Fix2/f-Fix4
Used to select between f-Fix2 and f-Fix4
Low = f-Fix2
High = f-Fix4
Select f-Fix4/AI1 REF Used to select between f-Fix4 and the analog setpoint value (terminal 6)
Low = f-Fix4
High = Analog setpoint value
Abbreviation
Meaning
Fixed Bit 1 Bit 0
f-Fix1 (P-20)
0 0
f-Fix2 (P-21)
0 1
f-Fix3 (P-22)
1 0
f-Fix4 (P-23)
1 1