6 Parameter structure
6.4 Control signal terminals
128 DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com
6.4.2.2 P-12 = 1: digital setpoint value, 1 operating direction
Table 34: P-12 = 1: digital setpoint value, 1 operating direction
The setpoint value is set using the keypad = digital setpoint value. The arrow
buttons are used to adjust the setpoint value.
P-15 DI1
(terminal 2)
DI2
(terminal 3)
DI3/AI2
(terminal 4)
DI4/AI1
(terminal 6)
0 START UP DOWN No function
1 Not permissible
2 START UP DOWN Select DIG REF/f-Fix1
3 START UP EXTFLT DOWN
4 START UP Select DIG REF/AI1 REF AI1 REF
5 Not permissible
6 START No function EXTFLT Select DIG REF/f-Fix1
7
START Select Quick‐dec EXTFLT Select DIG REF/f-Fix1
8 Not permissible
9 Not permissible
10 Not permissible
11 Not permissible
12 Not permissible
13 START No function EXTFLT No function
14 Not permissible
15 START Select f-Fix/DIG REF Select Fire Mode/Normal OP Select f-Fix4/f-Fix2
16 START Select f-Fix4/DIG REF Select Fire Mode/Normal OP No function
17 START Select DIG REF/f-Fix4 Select Fire Mode/Normal OP No function